Precautions For Fire And Explosion Prevention Of PE Storage Tanks

Sep 27, 2024

Leave a message

1. The base of the breathing valve and hydraulic safety valve on the PE storage tank should be equipped with flame arresters. Fire arresters should be inspected at least once a quarter.
2. Flexible hose compensators should be installed on the inlet and outlet oil pipelines of oil storage tanks.
3. The steel oil storage tank body should be equipped with lightning protection and anti-static grounding devices, and its grounding resistance should not exceed 10 Ω. At least one grounding point should be set every 30m along the bottom edge of the tank, and there should be no less than two grounding points for a single tank.
4. Every spring, a comprehensive inspection of lightning protection and anti-static grounding devices should be conducted, and the grounding resistance value should meet the requirements.
5. Two soft copper wires with a cross-sectional area of not less than 25mm ² should be used to connect the floating vessel and the tank wall of the floating roof tank.
6. The oil level in the storage tank should be operated within the safe tank position.
7. When the oil level of the condensate is higher than that of the heating coil, it should be heated with a steam riser first, and then heated with a steam coil after the condensate dissolves.
8. Chemical fiber clothing and shoes with iron nails should not be worn. Non explosion proof flashlights should not be turned on or off at the top of the tank.
9. Hot work and tank cleaning operations for oil pipelines in the storage tank area shall comply with industry regulations.
10. If the oil storage tank catches fire, all operations related to the burning tank should be immediately reported and stopped. Organize fire extinguishing and timely activate emergency plans.
11. Fire and explosion prevention in oil storage tanks and tank areas shall comply with the provisions of GB50183 and GB50074. Low expansion air foam fire extinguishing system shall comply with GB50151.
12. The storage tank area should be kept clean, and there should be no hay, oil stains, or combustibles inside the fire dike.

 